Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2013 | FIRE - ALARM FINAL | Approved | ||
| 10/01/2013 | FIRE - ALARM FINAL | Denied | Need all signage posted per code and manufacture requirements- ie. CAUTION, NOTICE, SYSTEM ABORT ect. Need lock outs installed on all breakers for the FACP and Vesda system Need dates when dates where install on all batteries Label inside FACP where breakers are located and breaker number Shall add the extra braces behind the circuit boards in the FACP's, when silencing the alarm one panel zero out and we had to reset system. Need an air leak test done on the buildings copy of the reports needed for the fire department TFD. |