Permit: T12PL00075

Parcel: 13637265A

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/27/2012 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) AN OLD GAS FLEX CONNECTOR CANNOT BE REUSED
2) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS OF VENT CONNECTOR
3) DO NOT USE TAPE ON VENT SYSTEM
4) TAPE IS NOT TO BE USED AS A BANDAID
5) YOU CANNOT USE FLEX COPPER ON A T & P DRAIN LINE
6) MUST BE SMOOTH 3/4" INTERNAL DIAMETER
7) THE VENT CONNECTOR DOES NOT FIT PROPERLY ONTO THE DRAFT DIVERTER