Permit: T12OT01405

Parcel: 11506107B


Addresses:

1910 N STONE AV

Inspection Status: Partial Approval

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
10/11/2012 FIRE - FINAL Partial Approval OK for temporary C of O through November 15, 2012. Full required alarm system not installed, but in lieu of approved alarm system, sprinkler system is monitored with a dialer, emergency lighting and emergency voice/alarm communications provided by fire watch personnel.