Case: T12DV01863

Parcel: 122070550


Addresses:

4407 E LINDEN ST

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
03/12/2012 INSP - INITIAL CODE ENFORCMENT Approved VISITED SITE, MET WITH TFD INVESTIGATORS. ELECTRICAL TO STRUCTURE WAS ISOLATED AT THE MAIN SERVICE PANEL BY TEP. S/W GAS SHOWED NO GAS TO THE ADDRESS. FIRE STARTED IN DETACHED GARAGE WHICH APPEARED TO HAVE BEEN ENCLOSED AND BEING USED AS LIVING SPACE. RENTORS DENIED ANYBODY WAS LIVING INSIDE. OCCUPANT TAMMY COGGINS MENTIONED PROPERTY WAS OWNED BY DEED AND NOTE TRADERS, HER FAMILY WAS RENTING TO OWN. UPON ENTRY FOUND ALL ELECTRICAL THROUGHOUT THE STRUCTURE HAD BEEN INSTALLED IN A HAZARDOUS MANOR, ALL WIRING WAS EXPOSED AND ALL OUTLETS, SWITCHES, AND LIGHT BOXES AND FIXTURES WERE ADDED TO THE OUTSIDE OF THE WALLS AND CEILING. ONE 20 AMP BREAKER FED THE STRUCTURE FROM THE MAIN SERVICE PANEL. NO SUB PANEL WAS FOUND INSIDE THE ENCLOSED GARAGE, PLYWOOD COVERED THE OPENING WHERE ELECTRICAL ENTERED THE BUILDING. FIRE STARTED AT A ELECTRICAL OUTLET. rAFTERS WERE UNDERSIZED AND OVERSPANNED NOW FIRE DAMAGED. ROOF SHEATHING FIRE DAMAGED AND FRAMED PONY WALL ON TOP OF 5 FT BLOCK WALL WAS ALSO FIRE DAMAGED, STUDS OVERSPANNED AND LACKING A DBL TOP PLATE. ORIGINAL GARAGE OPENING NOW ENCLOSED IS NOT PROPERLY CONSTRUCTED. TAMMY COGGINS MENTIONED BOTH MAIN STRUCTURE AND GARAGE WERE BUILT PRIOR TO 1950. EMERGENCY NOV TO VACATE WAS ISSUED AND STRUCTURE POSTED UNFIT TO OCCUPY. BOARDING NOT REQUIRED. SEE ADDITIONAL NOTES IN CASE PACKET.