Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/20/2013 | FIRE - FINAL | Approved | ||
| 02/11/2013 | FIRE - FINAL | Partial Approval | Temporary C of O approved Okay to use building to get final C of O will need to install an commercial FM/UL approved fire alarm/monitoring system. Need to get an approved plan and permit for this installation. | |
| 01/28/2013 | FIRE - FINAL | Denied | Correct sprinkler coverage in office northeast head is 8' off two walls only one wall allowed. Correct uprights sprinkler coverage in warehouse by east wall against office. Need to install a fire alarm system to monitor fire sprinkler system. Need to install a key box for access. Need separate plan and permit before any sprinkler or alarm work can be done. |