Permit: T12CM07696

Parcel: 14026023A


Addresses:

6393 S CAMPBELL AV


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T12CM07696

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/11/2013 FIRE SPKLR - FINAL Approved
01/28/2013 FIRE SPKLR - FINAL Denied Correct sprinkler coverage in office northeast head is 8' off two walls only one wall allowed.
Correct uprights sprinkler coverage in warehouse by east wall against office

Need separate plan and permit before this work can be done.