Permit: T12CM07328

Parcel: 11454057F

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
09/11/2013 FIRE - FINAL Approved
08/29/2013 FIRE - FINAL Denied 1. In Data/Tech room sprinkler head blocked by insulation
2. North part of building on sales floor insulation sitting on top of sprinkler heads, need to move insulation off of sprinkler heads min 1" inch throughout building.
3. In electrical room insulation on sprinkler heads.
4. Address numbers posted on building per handout given.
08/27/2013 FIRE - FINAL Denied 1. In Data/Tech room sprinkler head blocked by insulation
2. North part of building on sales floor insulation sitting on top of sprinkler heads, need to move insulation off of sprinkler heads min 1" inch throughout building.
3. In electrical room insulation on sprinkler heads.
4. Rear exit door outside back up lighting failed test need to replace.
5. Address numbers posted on building per handout given.