Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T12CM05861
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/19/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/17/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
04/12/2013 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
04/10/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
04/09/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
04/09/2013 | ELECTRIC - FINAL | Partial Approval | 1) PLANS DO NOT REFLECT WORK DONE ON SITE FOR SERVICE EQUIP, SIZE, AIR, RATINGS. BUSHINGS NOT INSTALLED WHERE NECESSARY PER CODE. 2)GUTTER CONDUCTORS TO BE DERATED PER 366.23 3) CONDUIT FITTINGS NOT SEATED PROPERLY 110-12, 250 NEC. 4)SUPPLY SIDE GROUNDING NEED TO COMPLY WITH 250-102C 5) HARDWARE FOR GUTTER 110-26 6) BONDING OF WATER BLD. STEEL NEED TO BE SUPPORTED. 7) BONDING TERM. LUG TO BLD. STEEL NOT PROPERLY TERMINATED. |