Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T12CM05572
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2013 | FIRE - FINAL | Approved | ||
| 03/27/2013 | FIRE - FINAL | Partial Approval | OKAY TO USE BUILDING To get C of O do the following: 1.) Label riser room door "RISER ROOM" 2.) Instal FD key box on riser room door |
|
| 03/25/2013 | FIRE - FINAL | Denied | 1. Remove slide bolt lock from front entrance doors 2. Install fire extinguishers every 75 feet 2A 10BC 3. Install panic hardware on north gate to exit out of patio (northside of church) 4. Need fire alarm installed and working 5. Lower storage by cry room for chairs have taped sprinkler heads 6. Need to add sprinkler coverage under walkway north side this cover is part of the exiting egress from the church; cover is constructed of all wood timber. 7. Metal awning cover by main electrical, north east corner of building shall be sprinkler this metal is non-combustible, but a person on site during inspection stated that it will be use for storage of a golf cart therefore any combustible storage requires sprinkler coverage. 8. Need as builds for the sprinkler changes. |