Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - FINAL
Permit Number - T12CM05090
Inspection Description - FIRE - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/05/2012 | FIRE - FINAL | Denied | Replace taped and painted heads in the following areas: TV section, Recliners, dinning room tables. X10 Remove two heads next to duct work need to be 4" inches or more away by TV's and Recliners area. In janitors closet install a ceiling or extend walls all the away to the deck or install uprights above ceiling throughout office and restrooms. Need new cal plate. Need a clear access to the inspectors' valve on the southwest corner wall. Need to test the flow switch with the inspectors test valve that is buried behind the wall southwest corner. Need lock out on breaker for alarm panel. |
|
12/05/2012 | FIRE - FINAL | Approved |