Permit: T12CM05090

Parcel: 12801007A


Addresses:

5530 E BROADWAY BL

Inspection Status: Denied

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
12/05/2012 FIRE SPKLR - FINAL Denied Replace taped and painted heads in the following areas: TV section, Recliners, dinning room tables. X10
Remove two heads next to duct work need to be 4" inches or more away by TV's and Recliners area.
In janitors closet install a ceiling or extend walls all the away to the deck or install uprights above ceiling throughout office and restrooms.
Need new cal plate.
Need a clear access to the inspectors valve on the southwest corner wall.
12/05/2012 FIRE SPKLR - FINAL Approved