Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T12CM04972
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/14/2013 | ELECTRIC - FINAL | Approved | PER SIGNED JOB CARD | |
05/09/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
05/09/2013 | ELECTRIC - FINAL | Partial Approval | 1. BOXES MORE THAN 1/4" OR 1/8" 314.20, 314.21 2. LABEL CONTACTORS & TIME CLOCKS 3. LABEL LIGHTING TO AREAS 908.4 4. BOND DISCONNECT ENCLOSURE 5. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM BOTTOM OF PANELS 6. PLANS NOTE "HANDLE LOCK ON" - IS CIRCUIT #35 EMCS PANEL THE CIRCUIT FOR THIS DEVICE 7. DISCONNECT B-1 OVER FIRE RISER STATION TUBE MOVED PER RAY MAJUTA |
|
04/17/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |