Permit: T12CM04806

Parcel: 11712087C


Addresses:

1 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T12CM04806

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/24/2014 FIRE - FINAL Approved
01/28/2014 FIRE - FINAL Denied Non-listed smoke detector installed in trash shoot rooms & not connected to the fire alarm system
01/24/2014 FIRE - FINAL Partial Approval 1. Install smoke detector in trash chute room and wire to alarm panel to shut down fire/smoke damper.
2. Add star of life symbols on each side of elevator doors main floor
3. Need elevator key to open door in key box
4. Need all subcontractor permit call in and cleared out i.e. Alarm Company.
01/21/2014 FIRE - FINAL Partial Approval Temporary fire final Approved for residents to move in to get final fire final the following shall be completed:
1. Between 4th and 5th stair landing emergency lighting failed east
2.4th floor exit signs not working on emergency power in lobby
3. Doors in stairwells failed to unlock during emergency power
4. Sprinkler bell failed when tested
5. When fire pump was switched off came in as 7th floor trash chute and fire pump??
6. In key boxes need label all keys and need key for the electrical room added
7. Need elevator door opener key
8. Per 2006 IBC section 716.3.2.1 you will need all fire/smoke dampers to close by detectors and fire alarm activation.
12/26/2013 FIRE - FINAL Partial Approval Temporary fire final Approved for residents to move in to get final fire final the following shall be completed:
Emergency generator back power was tested and all floors passed.
1. 7th floor east stairwell failed to shut closed
2. 6th floor finish tape and mud on fire rate ceilings
3. Between 4th and 5th stair landing emergency lighting failed east
4. 4th floor east stairwell smoke gasket needed
5. 3rd floor east stairwell not closing
6. 4th floor exit signs not working on emergency power in lobby
7. Emergency phones do not work
8. Doors in stairwells failed to unlock during emergency power
9. Sprinkler bell failed when tested
10. When fire pump was switched off came in as 7th floor trash chute and fire pump??
11. In key boxes need label all keys and need key for the electrical room added
12. 3rd floor by west stairwell sprinkler head blocked by led lights 18" to 24" away from led
13. For interior exit stairway IBC & IFC 2006 & 2012 section 1020.1.5. & 1022.8 - add a directional exit sign(s) on ground level floor and an approved barrier is provided at level of exit discharge to prevent persons from unintentionally continuing into levels below.
14. Need elevator keys in key box and 3 recall and one elevator door opener
15. Per 2006 IBC section 716.3.2.1 you will need all fire/smoke dampers to close by detectors and fire alarm activation.
16. Need to install and test emergency key switch for main entrance doors
12/24/2013 FIRE - FINAL Denied 1. 3rd floor by west stairwell sprinkler heads blocked by led lights 18" to 24" away from led light
2. Need keys in key boxes.
3. For interior exit stairway IBC & IFC 2006 & 2012 section 1020.1.5. & 1022.8 - add a directional exit sign(s) on ground level floor and an approved barrier is provided at level of exit discharge to prevent persons from unintentionally continuing into levels below.
4. Install elevator key box inside one key to open elevator doors, 3 keys for the fire recall switches
5. Need test sprinkler bell for sprinklers
6. Per 2006 IBC section 716.3.2.1. #4 you will need all FIRE/SMOKE DAMPERS to close by smoke detectors.
7. Need to test the emergency phone system.
8. Need to go through all fire rated hallways and re-caulk any penetrations through the fire rated walls any person that is doing this work needs to be certificated and have proof on person showing the certification.
9. All commutations room needs smoke gasket seals on doors
10. All interior exit stairway doors needs smoke gasket seals
11. 7th floor east stairwell door not latching shut
12. Need to install and test emergency key switch for main entrance doors
13. Need to correct elevator gurney requirements or appeal to the fire chief for changes in the requirements. Appeal form and code sections were sent to you.
14. Need to test emergency backup lighting throughout building by shutting down power and running emergency generator.
12/18/2013 FIRE - FINAL Denied 1. Room 610 bathroom hole in wall
2. Room 708 Bedroom ceiling hole
3. Not all rooms finished need to completed before finals will be given
4. 3rd floor by west stairwell sprinkler heads blocked by led lights
5. Need key box installed with entry keys to enter building, main electrical room, fire pump and riser room, fire alarm panel room.
6. Need signs on doors to electrical room, fire pump/riser room, fire alarm panel room.
7. Sign each level in the stairwells
8. Add a discharge sign on ground level floor or a stop bar across at the stairs to stop people from going to the basement during emergencies.
9. Address number posted on building 12 inch size
10. Install elevator key box inside one key to open elevator doors, 3 keys for the fire recall switches
11. Clear the F.D.C. and mount the signage properly
12. All doors in the residential floor hallways shall be fire rated and self-closing, self-latching and with smoke gaskets.
13. Need sprinkler bell for sprinklers
14. Need all FIRE/SMOKE DAMPERS to close when the fire alarm is activated.
15. Need to test the emergency phone system.