Inspection History: FIRE - ALARM FINAL

Permit Number - T12CM04806

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/24/2014 FIRE - ALARM FINAL Approved
01/28/2014 FIRE - ALARM FINAL Denied Non-listed smoke detector installed in trash shoot rooms & not connected to the fire alarm system
01/24/2014 FIRE - ALARM FINAL Partial Approval Install smoke detector in trash chute room and wire to alarm panel to shut down damper.
01/21/2014 FIRE - ALARM FINAL Partial Approval 1. Test fire sprinkler bell
2. Test outside horn/strobe on roof top
3. All fire/smoke dampers shall close when fire alarm actives.
4. Need to check breakers for lock outs for alalrm and sprinkler bell.
12/18/2013 FIRE - ALARM FINAL Denied 1. Wire fire bell
2. Wire and test elevator operations
3. Install outside horn/strobe on roof top
4. All fire/smoke dampers shall close when fire alarm actives
5. Need to test smoke for elevators