Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T12CM04806
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/24/2014 | FIRE - ALARM FINAL | Approved | ||
01/28/2014 | FIRE - ALARM FINAL | Denied | Non-listed smoke detector installed in trash shoot rooms & not connected to the fire alarm system | |
01/24/2014 | FIRE - ALARM FINAL | Partial Approval | Install smoke detector in trash chute room and wire to alarm panel to shut down damper. | |
01/21/2014 | FIRE - ALARM FINAL | Partial Approval | 1. Test fire sprinkler bell 2. Test outside horn/strobe on roof top 3. All fire/smoke dampers shall close when fire alarm actives. 4. Need to check breakers for lock outs for alalrm and sprinkler bell. |
|
12/18/2013 | FIRE - ALARM FINAL | Denied | 1. Wire fire bell 2. Wire and test elevator operations 3. Install outside horn/strobe on roof top 4. All fire/smoke dampers shall close when fire alarm actives 5. Need to test smoke for elevators |