Inspection History Details
Inspection Status: Approved
Inspection History: STEM WALL/RETAINING WALL
Permit Number - T12CM04806
Inspection Description - STEM WALL/RETAINING WALL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/14/2013 | STEM WALL/RETAINING WALL | Approved | ||
05/20/2013 | STEM WALL/RETAINING WALL | Partial Approval | ||
05/06/2013 | STEM WALL/RETAINING WALL | Partial Approval | COLUMNS AND CORE WALLS OK THROUGH LEVEL 6. LEVEL 5 COLUMN AT F/10 REQUIRES REPAIR OR REPLACEMENT AS DETERMINED BY EOR | |
04/18/2013 | STEM WALL/RETAINING WALL | Partial Approval | ALL COLUMNS AND CORES OK TO LEVEL 5 | |
04/08/2013 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection :* DG COLUMES AND ELEVATOR CORE 4TH LEVEL |
|
03/06/2013 | STEM WALL/RETAINING WALL | Partial Approval | ALL COLUMNS AND WALLS THROUGH LEVEL 2 COLUMNS AND WALLS TO LEVEL 3 WEST SIDE |
|
02/26/2013 | STEM WALL/RETAINING WALL | Partial Approval | WALLS & COLS OK TO LEVEL TWO | |
01/11/2013 | STEM WALL/RETAINING WALL | Partial Approval | OK TO PLACE SHOTCRETE ON ALL BASEMENT WALLS FROM B/6 COUNTER-CLOCKWISE TO D/11 OK TO PLACE ALL COLUMNS EXCEPT LINE 5E,5F,6E,6F COLUMNS NOT BEING PLACED PENDING REVISION. |
|
12/28/2012 | STEM WALL/RETAINING WALL | Denied | A.M. INSPECTION REQUEST FOR CIP WALL LINE D/ FROM 3 - 4.5 ONLY. CORRECTIONS STILL NOT MADE PER DISCUSSION WITH FOREMAN AND STEEL CONTRACTOR FROM YESTERDAY. IT IS NOT ACCEPTABLE TO FIELD BEND PARTIALLY EMBEDDED REINFORCING STEEL. PLEASE REFERENCE PLAN NOTES AND ACI 318 SECTION 7.3.2. | |
12/28/2012 | STEM WALL/RETAINING WALL | Partial Approval | LINE D / 3-4.5 BASEMENT LEVEL OK TO PLACE. | |
12/27/2012 | STEM WALL/RETAINING WALL | Denied | CIP WALL LINE D MUST HAVE SLAB HOOKS AS DETAILED IN STRUCTURAL SHEETS. IT IS NOT ACCEPTABLE TO "FIELD BEND" PARTIALLY EMEBEDDED REINFORCING STEEL (ACI 318 CHAPTER 7) | |
12/27/2012 | STEM WALL/RETAINING WALL | Denied | LATE INSPECTION MADE 4:30 PM AT REQUEST OF LUIS CARRAZA. CORRECTIONS NOTED FROM A.M. INSPECTION HAVE NOT BEEN MADE. |