Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2013 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 12/07/2012 | PLUMBING - FINAL | Denied | TYPE B VENT MAY NOT BE CUT. REPLACE DAMAGED B VENT. TAPE MAY NOT BE USED AT B VENT CONNECTION. CHECK FOR PROPER TERMINATION. RELIEF VALVE MAY DISCHARGE INTO PAN ONLY WHEN THERE IS NO GRAVITY DRAIN TO EXTERIOR. LOWER EXISTING DRAIN IN WALL AND CONNECT WH RELIEF VALVE TO IT. IF EXISTING DRAIN DOES NOT GO OUTSIDE, ALIGN DRAIN PAN TO CATCH DISCHARGE |