Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2013 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 02/26/2013 | BUILDING - FINAL | Not ready for Inspection | PROVIDE 1" AIR GAP BETWEEN CONDENSATE DRAIN AND FLOOR DRAIN ITEMS 2 AND 3 DATED 12-19-12 NOT COMPLETE |
|
| 12/19/2012 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1.HYDRONIC PIPING AT HOT WATER SIDE LEAKING 2. PROVIDE SUN SHIELDS AT FLEXIBLE CONNECTORS 3. PROVIDE BALANCE REPORT DRY AND WET 4. HYDRONICS NOT PER PLAN SEE DETAIL S-M2.1 |