Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/16/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BACK FEED BREAKER TO HAVE MANUFACTURES HOLD DOWN 2. CLEAN SURFACE UNDER GROUND BAR 250.12 + LUGS CAN NOT USE DRY WALL SCREWS TO HOLD BAR 250.8 3. ONLY ONE WIRE PER LUG TERMINATION 4. BOND SERVICE NIPPLE TO PANEL 5. PROVIDE FULL GROUNDING ELECTRODE SYSTEM 6. LABEL SERVICES AS TO HIGH LEG MARKING 7. FINISH PREVIOUS ITEMS 1,2,3,5,7,8,9 |
|
| 06/26/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/22/2012 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/20/2012 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |