Permit: T12CM03546

Parcel: 10715001B


Addresses:

2795 N 1ST AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/08/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/16/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BACK FEED BREAKER TO HAVE MANUFACTURES HOLD DOWN
2. CLEAN SURFACE UNDER GROUND BAR 250.12 + LUGS CAN NOT USE DRY WALL SCREWS TO HOLD BAR 250.8
3. ONLY ONE WIRE PER LUG TERMINATION
4. BOND SERVICE NIPPLE TO PANEL
5. PROVIDE FULL GROUNDING ELECTRODE SYSTEM
6. LABEL SERVICES AS TO HIGH LEG MARKING
7. FINISH PREVIOUS ITEMS 1,2,3,5,7,8,9
06/26/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/22/2012 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
06/20/2012 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*