Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2012 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 07/16/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 06/26/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAINTAIN WORKING CLERAENCE SUB PANEL 2) FILL UNUSED OPENINGS & BOX COVERS, RO SEALS, MISSING PLATES 3) SUPPORT CONDUIT RACEWAYS INTERIOR, EXTERIOR ROOF 4) WATER HEATER NOT CORD & PLUG CONNECTED 5) MISSING SERVICE CONDUCTERS 6) CAN NOT FORK GROUND CONDUCTOR 7) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS 8) MISSING GROUNDING ELECTRODE CONDUCTOR 9) NEED VERIFICATION OF NEW A/C PERMIT & WIRING 10) EXPOSED CONDUCTERS ROOF |
|
| 06/22/2012 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* | |
| 06/20/2012 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* |