Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T12CM03078
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/28/2012 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
12/27/2012 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* NO CONTRACTOR ON SITE. ELEC. CONTRACTOR NEEDS TO BE ON SITE. | |
12/24/2012 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
12/19/2012 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. MAINTAIN WORKING CLEARANCE FOR A/C DISCONNECT 2. SECURLY ATTACH FIXTURES TO GRID 3. VERIFY BOX FILL 4. SUPPORT M/C FIXTURE WHIPS OFF OF GRID & ABOVE PANEL 5.SEAL UNUSED CONDUIT OPENINGS 6. VDV CABELING TO BE INDEPENDENTLY SUPPORTED 300.11, 760.24 7. M/C TO BE INDEPENDANTLY SUPPORTED 8. SUPPORT SECURE MECHANICL REGISTERS |
|
10/31/2012 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | PROVIDE PEOTECTION WHERE ABS PASSES THROUGH METAL STUDS, PROVIDE A TEST ON PLUMBING FRONT HALF OF BUILDING OK TO SHEET ROCK AREAS WITHOUT PLUMBING | |
10/29/2012 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
10/19/2012 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |