Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
05/29/2012 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FILL UNUSED PORTION OF OPENING IN PANEL SIDE AND BACK
2) ONLY ONE NEUTRAL CONDUCTOR PER TERMINAL CONNECTION
3) LUG FOR GROUNDING NOT CODE COMPLIANT 250.8 & 250.12
4) INSTALL MAIN BONDING SCREW
5) SECURE CONDUIT SIDE OF PANEL
6) SMOKE DETECTORS NEEDED IN ALL BEDROOMS
7) CORDS NOT ALLOWED IN OR THRU WALLS
8) KITCHEN RECEPTS TO BE GFCI PROTECTED
9) MISSING LIGHT FIXTURE
10) FAN IN BATHROOM NOT CODE COMPLIANT 410.4
11) IT APPEARS ADDITIONS FOR BATHROOM AND STORAGE MAY HAVE BEEN BUILT WITH OUT PERMITS. PLEASE VERIFY PERMITS IF NOT MUST BE PERMITTED