Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/29/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FILL UNUSED PORTION OF OPENING IN PANEL SIDE AND BACK 2) ONLY ONE NEUTRAL CONDUCTOR PER TERMINAL CONNECTION 3) LUG FOR GROUNDING NOT CODE COMPLIANT 250.8 & 250.12 4) INSTALL MAIN BONDING SCREW 5) SECURE CONDUIT SIDE OF PANEL 6) SMOKE DETECTORS NEEDED IN ALL BEDROOMS 7) CORDS NOT ALLOWED IN OR THRU WALLS 8) KITCHEN RECEPTS TO BE GFCI PROTECTED 9) MISSING LIGHT FIXTURE 10) FAN IN BATHROOM NOT CODE COMPLIANT 410.4 11) IT APPEARS ADDITIONS FOR BATHROOM AND STORAGE MAY HAVE BEEN BUILT WITH OUT PERMITS. PLEASE VERIFY PERMITS IF NOT MUST BE PERMITTED |