Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/05/2012 |
MECHANICAL - FINAL |
|
Denied |
1. Half inch gas pipe is undersized for 98000 BTUs. install a 3/4" supply pipe, to within six feet of the gas pack. 2. Support the gas pipe. 3. Terminate condensate pipe at ground level. |