Inspection History Details
Inspection Status: Denied
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDING ELECTRODE CONDUCTOR TO BE TO ALL MICRO INVERTERS 2) GEC CONNECTIONS TO BE IRREVERSIBLE 250.64 3) USE APPROVED CONNECTIONS TO JUNCTION BOX 4) PLEASE PROVIDE DETAIL FOR MISSION TILE 5) CHECK ATTIC NEXT TIME-10" RULE |
|
| 03/09/2012 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) GATE LOCKED AND NO ANSWER AT DOOR |