Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESS TEST FNL
Permit Number - T12CM00160
Inspection Description - PLUMBING - GAS PRESS TEST FNL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/09/2012 | PLUMBING - GAS PRESS TEST FNL | Approved | IVRS - Inspection :* | |
04/25/2012 | PLUMBING - GAS PRESS TEST FNL | Not ready for Inspection | IVRS - Inspection :* 1) HAVE YOUR SITE NUMBER ADDED TO YOUR PERMIT 2) HAVE PLAN REVIEWER STAMP PLAN 3) WHAT IS TOTAL DISTANCE FROM METER ? , DRAWING NOT REFLECTIVE OF WHAT'S INSTALLED. SHOW LOCATION AND INSTALL ANSUL VALVE 4) INCLUDE ALL NEW WORK 5) APPROVED PLAN TO SHOW LOCATION OF ALL FIXTURES/APPLIANCES 6) ALL 3 HAND SINKS ARE CURRENTLY INDIRECTLY WASTED 7) CORRECTIONS NEED TO BE MADE ON THE 3 COMP SINK 8) WATER HEATER (2 OF THEM) ABOVE RESTROOM ARE LEAKY AND LOOK DANGEROUS. THEY ARE NOT IN PAN, COPPER AND GALVANIZED MIXED, NO EXPANSION TANK. INCLUDE THIS WORK ON THE PLAN |