Permit: T12CM00073

Parcel: 12709016A


Addresses:

5545 E BROADWAY BL

Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Date Description Inspector Results Comments
11/28/2012 FIRE SPKLR - UG, PIPING, HYDRO Approved 200 PSI FOR HOURS
11/05/2012 FIRE SPKLR - UG, PIPING, HYDRO Denied As stated in July 07, 2012 inspection you will need a separate plan and permit for underground work, I called sprinkler contractor Allen fire to call construction contractor and advised him that we will not be coming out until separate permit for underground is approved.
07/05/2012 FIRE SPKLR - UG, PIPING, HYDRO Denied 1.) Looked at 6 foot stub out with 11 feet piping all ductile need to wrap all piping in PVC plastic with install tracer wire also 200 PSI test for 2 hours approved.
2.) Advise construction supervisor that they will need to get a separate approved plan and permit for the installation of the underground.