Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T12BU01082

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/26/2013 FIRE SPKLR - FINAL Approved
07/23/2013 FIRE SPKLR - FINAL Partial Approval tested all flow switches and tampers.
07/16/2013 FIRE SPKLR - FINAL Partial Approval Partial approval given for moving in furniture when Kazal turns on sprinkler system with fire pump on line, Tested emergency switch over with fire pump running, emergency generator switched over in 19 seconds fire pump started back up no problems.

Still need to test FACP to fire pump and generator.
07/08/2013 FIRE SPKLR - FINAL Partial Approval completed a flow test with pump rep.
2. still need to test with alarm installed alarm was not installed.
3. need to perform a generator test this was not hooked up.