Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T12BU00517

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/19/2012 FIRE SPKLR - FINAL Approved
09/21/2012 FIRE SPKLR - FINAL Not ready for Inspection 1. FIRE PUMP NOT READY. FAILED CRANK TO FAIL TEST. BATTERIES WENT DEAD. ONE BATTERY NEEDS TO BE REPLACED FILL CAP MISSING AND SHIPPING STRAP WAS BROKEN UPON DELIVERY. I WAS INFORMED BY THE ACTUAL FIRE PUMP ENGINEER THAT IF ANY DEBRIS IS IN THE BATTERY FROM THE MISSING CAP THE BATTERY IS NOT ANY GOOD AND WILL FAIL.
2. TANK VENTS ON ROOF NEED CAPS ON THEM THEY ARE WIDE OPEN AND WATER AND DEBRIS CAN ENTER TANK.
3. DIESEL TANK IS ALMOST EMPTY.
4. NEED FUEL FILLING LINE TO BE INSTALLED LEADING OUT SIDE OF BUILDING CHECK SPRINKLER PLANS FOR INSTALLATION SPECS.
09/20/2012 FIRE SPKLR - FINAL Denied 1. Room next to subway shop for future use needs walls all the way to the deck or install drop ceiling with pendents or uprights throughout.
2. Taped heads above cold coolers on sale floor (eastside). Painted head on sales floor in front of kitchen area (against wall).
3. IFC 912.4 Signs; need sign for the test header stating "TEST CONNECTION" copy of code section given.
4. Need 200 psi for 2 hour test on system 2 for 24' of 6" pipe that was replaced.
5. Need fire pump test done before calling in for fire final.
6. Remove sprinkler heads in the con-x box for the fire alarm and electrical panels.