Inspection History Details
Inspection Status: Partial Approval
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2011 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) 13 PSI TEST IS OK 2) LEFT GAS CARD 3) IS USING A COMMON VENT FOR FURNACE AND WATER HEATER, THE HEATER MUST CONNECT IN THE BOTTOM OF TEE. IF YOU USE THE ABANDONED 3" DBL WALL, EXTEND IT 3' ABOVE COMBUSTION AIR INTAKE |
|
| 12/02/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE A 10 PSI AIR TEST ON HOUSE PIPING 2) PROVIDE CORRECT VENTING FOR WATER HEATER/FURNACE (REPLACED WITHOUT INSPECTION) 3) PROVIDE CORRECT RELIEF DRAIN PIPING WITHOUT TRAP 4) CITY OF TUCSON HANDOUT PROVIDED 5) METER IS LOCKED OFF DUE TO LEAK |