Permit: T11ME00297

Parcel: 137320270

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/14/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE ELECTRICAL ROOF JACK
2) PVC CONDENSATE DRAIN IS TO BE BLOCKED UP OFF ROOF MINIMUM 1.5"
3) PVC CONDENSATE NOT PROPERLY TERMINATED
4) ALL PVC JOINTS ARE TO HAVE PRIMER PRIOR TO GLUE, PRIMER IS TO BE PURPLE IN COLOR
5) ALL PVC PIPE EXPOSED TO DAYLIGHT IS TO BE COATED TO PROVIDE U.V. PROTECTION