Permit: T11ME00271

Parcel: 13613027J

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/27/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/06/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
A/C UNIT REQUIRE 35 AMP OVERCURRENT PROTECTION
HEAT STRIP REQUIRES 30 AMP
40 AMP BREAKS NOT ADEQUATE FOR A/C W/HEAT STRIP