Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/27/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/06/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* A/C UNIT REQUIRE 35 AMP OVERCURRENT PROTECTION HEAT STRIP REQUIRES 30 AMP 40 AMP BREAKS NOT ADEQUATE FOR A/C W/HEAT STRIP |