Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T11FR01063
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/15/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 1. In the D.E.S. office - Pendent sprinkler head too far off wall. NOTE: You will need a permit to move head or heads will need a plan and a permit if adding any heads. 2. OS&Y valve doesn't close completely, nut is breaking. - Shall repair or replace valve. 3. Replace gauges due to age & 3-way valves due to corrosion. - Shall recalibrate or replace gauges and replace 3 way valves. |