Case: T11FR01063

Parcel: 10603079C


Addresses:

3202 N ORACLE RD

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
09/15/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required 1. In the D.E.S. office - Pendent sprinkler head too far off wall. NOTE: You will need a permit to move head or heads will need a plan and a permit if adding any heads.
2. OS&Y valve doesn't close completely, nut is breaking. - Shall repair or replace valve.
3. Replace gauges due to age & 3-way valves due to corrosion. - Shall recalibrate or replace gauges and replace 3 way valves.