Case: T11FR01056

Parcel: 10408075N


Addresses:

4491 N ORACLE RD

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
02/15/2012 VIOL - FIRE PROTECTION SYSTEMS Approved All repairs done by United Fire
09/15/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required 1. No sprinkler head box - Shall install sprinkler box
2. No spare sprinkler heads - Shall install proper amount of sprinkler heads.
3. No sprinkler wrench - Shall install proper sprinkler wrench
4. Inspector test valve inaccessible - Shall relocate inspector test valve for accessibility.
5. Perform main drain test - Shall replace gauges
6. Perform a 5 year check valve inspection
7. Main control is unsecured - Shall secure main drain by monitoring with approved alarm system or chain and lock.