Description:

Sprinkler Deficiencies

Completed Inspections

Case Status: COMPLETE
Case Number: T11FR01056
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
09/15/2011 VIOL - FIRE PROTECTION SYSTEMS CSCHULTZ Approved 1. No sprinkler head box - Shall install sprinkler box 2. No spare sprinkler heads - Shall install proper amount of sprinkler heads. 3. No sprinkler wrench - Shall install proper sprinkler wrench 4. Inspector test valve inaccessible - Shall relocate inspector test valve for accessibility. 5. Perform main drain test - Shall replace gauges 6. Perform a 5 year check valve inspection 7. Main control is unsecured - Shall secure main drain by monitoring with approved alarm system or chain and lock.
09/29/2011 INSP - REINSPECTION CSCHULTZ Approved All repairs done by united fire