Case: T11FR00929

Parcel: 11449030A

Inspection Status: Violation

Inspection History: VIOL - FIRE SERVICE FEATURES

Date Description Inspector Results Comments
04/26/2011 VIOL - FIRE SERVICE FEATURES Violation Fire Dept equipment signage:
510.1 Identification. Fire protection equipment shall be identified
in an approved manner. Rooms containing controls for
air-conditioning systems, sprinkler risers and valves, or other
fire detection, suppression or control elements shall be identified
for the use of the fire department. Approved signs required
to identify fire protection equipment and equipment location,
shall be constructed of durable materials, permanently
installed and readily visible.

______ Place a sign in Red on White stating "Fire Riser Room" or somthing of this nature. 2" or 3" letters.
04/26/2011 VIOL - FIRE SERVICE FEATURES Violation Electrical Room Label:
605.3.1 Labeling. Doors into electrical control panel rooms
shall be marked with a plainly visible and legible sign stating
ELECTRICAL ROOM or similar approved wording.
The disconnecting means for each service, feeder or branch
circuit originating on a switchboard or panelboard shall be
legibly and durably marked to indicate its purpose unless
such purpose is clearly evident.

______ Place a sign "Electrical Room" in 2" Red on White on the Electrical room door.