Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - FIRE SERVICE FEATURES
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2011 | VIOL - FIRE SERVICE FEATURES | Violation | Fire Dept equipment signage: 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. ______ Place a sign in Red on White stating "Fire Riser Room" or somthing of this nature. 2" or 3" letters. |
|
| 04/26/2011 | VIOL - FIRE SERVICE FEATURES | Violation | Electrical Room Label: 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. ______ Place a sign "Electrical Room" in 2" Red on White on the Electrical room door. |