Case: T11FR00929
Case Details
Entered Date:
04/26/2011
Applicant:
RINCON MOUNTAIN PRESBYTERIAN CHURCH INC
Description:
Full inspection done 4/26/2011; Paul Marien - 603-6374 / Phil Kruis- 327-2390 / A-3 occupancy / Very well maintained - Good job!
Outstanding Inspections
Case Number: T11FR00929
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2011 | INSP - FULL | BCOBB | Violation | Please correct the following Tucson Fire Code violations: Notes: 1. C of O to be provided upon re-inspection, if available. If not available, manager will be in the process of acquiring it. Certificate of Occupancy [C of O]: 1997 Uniform Administrative Code Section 309.5 Posting. The certificate of occupancy shall be posted in a conspicuous place on the premises and shall not be removed except by the building official. ______ Acquire a C of O from Developmental Services. [791-5550] ___OK___ C of O on site. [Very good] 2. A record of the sprinkler system inspections shall be made available upon re-inspection. Sprinkler system: 903.5 Testing and maintenance. Sprinkler systems shall be tested and maintained in accordance with Section 901. __OK___ System to be tested, and tagged annually. [All deficiencies abated, and a copy of the report to be on the premises] |
| 04/26/2011 | VIOL - FIRE SERVICE FEATURES | BCOBB | Violation | Electrical Room Label: 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. ______ Place a sign "Electrical Room" in 2" Red on White on the Electrical room door. |
| 04/26/2011 | VIOL - FIRE SERVICE FEATURES | BCOBB | Violation | Fire Dept equipment signage: 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. ______ Place a sign in Red on White stating "Fire Riser Room" or somthing of this nature. 2" or 3" letters. |
| 04/26/2011 | VIOL - FIRE RESIST.RATED CONST | BCOBB | Violation | Missing, Damaged or Moved ceiling tiles: TFC2006/ 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. _____Replace missing or damaged ceiling tiles. [Riser room / Electric room] |
| 04/26/2011 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Violation | Escutcheons: 903.3.1 Standards. Sprinkler systems shall be designed and installed in accordance with Sections 903.3.1.1, 903.3.1.2 or 903.3.1.3. ______ Repair or replace above item as necessary. |
| 04/26/2011 | VIOL - MEANS OF EGRESS | BCOBB | Violation | Emergency lighting: IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights. [and add to "classroom study hall and storage room"] |
| 04/26/2011 | VIOL - MEANS OF EGRESS | BCOBB | Violation | Exit Signs- light and back up power: 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. ______ Repair all exit signs and battery back up system. |