Case: T11FR00892

Parcel: 117050240


Addresses:

412 N 4TH AV


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T11FR00892

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
04/22/2011 VIOL - MEANS OF EGRESS Correction Required 1008.1.8.3 Locks and latches.
Locks and latches shall be permitted to prevent operation of doors where any of the following exists…
-- 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress
side provided:
-- 2.1. The locking device is readily distinguishable as locked,
-- 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background,
-- 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause.

_____ Place the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" visibly above your main
egress door.

1008.1.8.4 Bolt locks.
Manually operated flush bolts or surface bolts are not permitted.

_____ Remove the slide bolt from the KICTHEN egress door, as bolt lock of any kind are not permitted

1027.3 Exit sign illumination.
Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose.

_____ Fix, repair, and/or replace all non-working exit signs in order to meet code standards





________________________________________________
(Joseph P. Longo, Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report.
(Building Representative)

____________________________
(Captain)

Re-inspection scheduled on or after ___/___/___
Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions.
Thank you.

Re-inspection passed: ___ ___ ___


___________________ Passed on: ________
(Joseph P. Longo)