Case: T11FR00869

Parcel: 13615383A


Addresses:

2699 S PANTANO RD


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T11FR00869

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
05/16/2011 VIOL - BUILDING SVCS & SYSTEMS Approved
04/20/2011 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.

" Relocate the waste oil tank