Case: T11FR00869

Parcel: 13615383A


Addresses:

2699 S PANTANO RD


Inspection Status: Approved

Inspection History: INSP - AST

Case Number - T11FR00869

Inspection Description - INSP - AST

Inspection Status - Approved

Date Description Inspector Results Comments
05/16/2011 INSP - AST Approved
04/20/2011 INSP - AST Correction Required Dear Sir or Madam,

The Tucson Fire Department has conducted a fire safety inspection at the above stated business on 04-19-2011. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code with modifications. A Re-inspection will be performed on or about 05-12-2011.


The tanks on your property must have a permit obtained through the City of Tucson. Below are the codes that require the permit and give the requirements for installation.

3404.2.7.3.2 Vent-line flame arresters and venting devices. Vent-line flame arresters and venting devices shall be installed in accordance with their listings. Use of flame arresters in piping systems shall be in accordance with API 2028.


3404.2.7.3.3 Vent pipe outlets. Vent outlets on atmospheric tanks storing Class IIIB liquids are allowed to discharge inside a building if the vent is a normally closed vent.
" Install the required vents, if the tanks are indoors install the "Normally closed or Pressure/ vacuum" type vent


3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. The venting shall be installed and maintained in accordance with Section 2.2.5.2 of NFPA 30.
" Install the required emergency vents.