Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T11FR00749
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/18/2011 | INSP - FULL | Approved | AST'S REFERRED TO CONRAD FUNKE FOR PERMIT APPROVAL. | |
03/30/2011 | INSP - FULL | Correction Required | 1. _____ 2703.5.1 Markings. Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner. Rooms or cabinets containing compressed gases shall be conspicuously labeled: -REAR YARD 2. _____ 105.6.16 #3 Flammable and combustible liquids. An operational permit is required to… store, handle or use Class II or Class IIIA or class IIIB liquids in excess of 25 gallons (95 L) in a building or in excess of 60 gallons (227 L) outside a building, except for fuel oil used in connection with oil-burning equipment. - SEE HANDOUT 3. _____ 310.3 "No Smoking" signs. The fire code official is authorized to order the posting of "No Smoking" signs in a conspicuous location in each structure or location in which smoking is prohibited. The content, lettering, size, color and location of required "No Smoking" signs shall be approved. 4 _____ 2703.3 Release of hazardous materials. Hazardous materials in any quantity shall not be released into a sewer, storm drain, ditch, drainage canal, creek, stream, river, lake or tidal waterway or on the ground, sidewalk, street, highway or into the atmosphere. |