Case: T11FR00688

Parcel: 120093120


Addresses:

4601 S 3RD AV

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
05/12/2011 VIOL - FIRE PROTECTION SYSTEMS Approved
03/23/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required 1. Coverage in conference room is too far off wall need 2 heads added. - Shall correct sprinkler coverage, Note: you will need to an approved plan and permit before work is done.
2. Coverage in hallway to men's restroom by filter room no head need to add 1 head. - Shall correct sprinkler coverage in hallway, Note: you will need an approved plan and permit before doing any work.
3. Need a 5 year check valve inspection done on both risers.
4. Shall replace all missing escutcheons - 1 in janitors closet, front employee lounge 1, women's restroom 1, in front men's restroom 1, 1 in Phoenix dispatch office, 1 in filter room.
5. Vehicle shop office 1 needs complete assembly - Shall replace escutcheon assembly.
6. Vehicle shop 3 corroded heads - Shall replace heads.
7. Upstairs storage head appears to be far off wall may need 2 heads added. - Shall correct sprinkler coverage, Note: you will need an approved plan and permit before work is done.