Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2011 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
| 03/23/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 1. Coverage in conference room is too far off wall need 2 heads added. - Shall correct sprinkler coverage, Note: you will need to an approved plan and permit before work is done. 2. Coverage in hallway to men's restroom by filter room no head need to add 1 head. - Shall correct sprinkler coverage in hallway, Note: you will need an approved plan and permit before doing any work. 3. Need a 5 year check valve inspection done on both risers. 4. Shall replace all missing escutcheons - 1 in janitors closet, front employee lounge 1, women's restroom 1, in front men's restroom 1, 1 in Phoenix dispatch office, 1 in filter room. 5. Vehicle shop office 1 needs complete assembly - Shall replace escutcheon assembly. 6. Vehicle shop 3 corroded heads - Shall replace heads. 7. Upstairs storage head appears to be far off wall may need 2 heads added. - Shall correct sprinkler coverage, Note: you will need an approved plan and permit before work is done. |