Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 1. Shall secure all valves to the sprinkler systems by monitoring the system with an approved 24 hour off site system or chain and padlocks. 2. Shall secure all Post Indicator Valve (PIV) with padlocks. 3. Shall repair all PIV's so that indicator part works and show if open or closed. 4. You shall immediately update the access code to the main gate and replace all keys to all gates. If found with an invalid code again, you will be required to install a key switch at the entrance pad. 5. Shall install a thumb turn style lock on front man gate so all visitors can exit property with out the use of a key. |
|
| 03/16/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 1. Shall repair Broken piping from February 2, 2011 freeze 2. Shall repair or replace water motor gong that failed test on riser # C-15 3. Shall add sprinkler coverage under lofts in building C-8. Note you will need an approved plan and permit to do this work. 4. Shall repair or replace bell on riser #3 5. Shall repair or replace bad check valve on riser #4 6. Shall insulate all piping below 2 inch from freezing weather. Will need to set up a fire watch until all sprinkler systems are back on line. A field notice on fire watch requirements was given and signed by owner. Re-inspection is set for April 12, 2011. |