Case: T11FR00641
Case Details
Entered Date:
03/16/2011
Applicant:
DOWNTOWN TUCSON STORAGE LLC
Description:
Sprinkler Deficiencies
Outstanding Inspections
Case Number: T11FR00641
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2011 | VIOL - FIRE PROTECTION SYSTEMS | CSCHULTZ | Correction Required | 1. Shall secure all valves to the sprinkler systems by monitoring the system with an approved 24 hour off site system or chain and padlocks. 2. Shall secure all Post Indicator Valve (PIV) with padlocks. 3. Shall repair all PIV's so that indicator part works and show if open or closed. 4. You shall immediately update the access code to the main gate and replace all keys to all gates. If found with an invalid code again, you will be required to install a key switch at the entrance pad. 5. Shall install a thumb turn style lock on front man gate so all visitors can exit property with out the use of a key. |
| 05/16/2011 | INSP - REINSPECTION | CSCHULTZ | Correction Required | Received a call from Quality tenant improvement fire protection asking for more time to get repairs done I granted a re-inspection date set for June 1, 2011. |