Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/21/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE PROPER FITTINGS AT EXTERIOR PANCAKE BOXES EXT. LIGHTIGN ROMEX TO BOX CONNECTORS 2) RECALL 02090 |
|
| 03/15/2012 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) EXISTING PANEL HAS BEEN REPLACED WITH A NEW PANEL 2) GROUND WIRING TO BE ON A SEPERATE BUS AS NEUTRAL WIRING 3) LB FITTINGS NEED COVER PLATES 4) NEW 1/2" FROM PANEL NEEDS ROOF JACK (WATER HEATER) |
|
| 03/13/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) UNIT LOCKED-NO MSG. 2) A REINSPECTION FEE WILL BE ASSESED NEXT INSPECTION IF NO ACCESS OR CODE COMPLIANCE |
|
| 12/06/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PANEL NOT GROUNDED. INSTALL GROUND ROD SYSTEM 2) DBL LUGGED 15 AMP CIRCUIT 7. SEAL UNUSED OPENINGS IN DEADFRONT 3) SEAL KNOCKOUTS AT PANEL 4) PROTECT WIRING LAUNDRY ROOM UNDER 7' FROM PHYSICAL DAMAGE 5) OMIT HAZARDOUS EXTERIOR LIGHT FIXTURES, NOT TO CODE 6) OMIT HAZARDOUS ZIP CORD BEDROOM LIGHT FIXTURE 7) RELOCATE ANY SMOKE ALARM WITHIN 36" FORCED AIR REGISTER. SMOKE ALARM HALLWAYS 8) MISSING OUTLETS DINING ROOM 9) INSTALL ADDED 220 IN APPROVED BOXES 10) ALL PORCH ADDITIONS SHOULD BE ON RECORD AND TO INCLUDE ELECTICAL 11) NOTES 1-9 FOR POWER |