Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2011 | ELECTRIC - FINAL | Approved | PANEL OK IN CLOSET AS THIS IS A SIMPLE REPAIR OF AN EXISTING CONDITION. GROUNDS & NEUTRALS SEPARATED UNUSED OPENINGS AT BACK OF PANEL ARE TO EXISTING BOX BEING USED AS RACEWAY. THEY DO NOT NEED TO BE FILLED. CABLE SHEATH IS FULL 2" INTO RACEWAY, CONDUCTORS TO BREAKER PANEL ARE NOT CLAMPED, SO THIS INSTALLATION MEETS CODE. EXISTING SE CABLE FROM ORIGINAL INSTALLATION HAS NOT BEEN TOUCHED. OK TO LEAVE AS IS FOR THIS REPAIR. |
|
| 11/23/2011 | ELECTRIC - FINAL | Denied | 1) PANEL NOT ALLOWED IN CLOSET 2) SEPARATE GROUNDS & NEUTRALS 3) FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON-COMBUSTIBLE PRODUCT 4) CABLE SHEATH TO BE 1/4" INTO ENCLOSURE 5) WILL NEED EQUIPMENT GROUND CONDUCTOR BACK TO SERVICE FOR PANEL GROUNDS-- WE HAVE A UNISOLATED GROUNDED/NEUTRAL CONDUCTOR HERE. |