Permit: T11EL03004

Parcel: 116142240


Addresses:

1934 W ANKLAM RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/29/2011 ELECTRIC - FINAL Approved PANEL OK IN CLOSET AS THIS IS A SIMPLE REPAIR OF AN EXISTING CONDITION.

GROUNDS & NEUTRALS SEPARATED

UNUSED OPENINGS AT BACK OF PANEL ARE TO EXISTING BOX BEING USED AS RACEWAY. THEY DO NOT NEED TO BE FILLED.

CABLE SHEATH IS FULL 2" INTO RACEWAY, CONDUCTORS TO BREAKER PANEL ARE NOT CLAMPED, SO THIS INSTALLATION MEETS CODE.

EXISTING SE CABLE FROM ORIGINAL INSTALLATION HAS NOT BEEN TOUCHED. OK TO LEAVE AS IS FOR THIS REPAIR.
11/23/2011 ELECTRIC - FINAL Denied 1) PANEL NOT ALLOWED IN CLOSET
2) SEPARATE GROUNDS & NEUTRALS
3) FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON-COMBUSTIBLE PRODUCT
4) CABLE SHEATH TO BE 1/4" INTO ENCLOSURE
5) WILL NEED EQUIPMENT GROUND CONDUCTOR BACK TO SERVICE FOR PANEL GROUNDS-- WE HAVE A UNISOLATED GROUNDED/NEUTRAL CONDUCTOR HERE.