Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/07/2011 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST ADDRESS ON BLDG VISIBLE FROM STREET 2) POST UNIT LETTER 3) HAZARDOUS WIRING AT 50 AMP CIRCUIT IN PANEL DUE TO VANDALISIM 4) LABEL CIRCUITS 5) WEATHERED COVER EXTERIOR OUTLET AT LAUNDRY 6) SUB PANEL NOT MAINTAINED IN WORKING CONDITION, HAVE QUALIFIED ELECTRICIAN OMIT VIOLATIONS 7) EXPOSED CONDUCTOR EXTERIOR OUTLET AT WATER HEATER 8) SECURE OUTLET DINING ROOM TO WALL 9) SMOKE ALARM BEDROOMS AND HALLWAY 10) 2 WIRE OUTLETS AND 2 WIRE OUTLETS WITH GROUND MIXED THROUGHOUT 11) WATER HEATER NOT TO CODE |