Permit: T11EL02100

Parcel: 113072350


Addresses:

1415 E ADELAIDE DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/18/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/16/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/13/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) FINISH #2 PREVIOUS
2) SPLIT BOLT FOR ONLY 2 CONDUCTORS-A RUN AND A TAP
3) NEED ACCESS TO SUB PANELS
09/07/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) CANNOT ENTER OR EXIT TOP END WALL PER MANUFACTURES INSTRUCTIONS
2) PROTECT CONDUCTORS 300.4
3) NEED ANIT OXIDE COMPOUND ON ALL ALUMINUM CONDUCTORS 110.3
4) CANNOT USE SHEET METAL THREAD SCREWS FOR GROUNDING 250.8
5) SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL & PROVIDE A NEUTRAL 250.24 & 200.6
6) SECURE "SE" CABLE TO BOX 312.5 (C)
7) PROVIDE PHYSICAL PROTECTION FOR "SE" CABLE
8) MAINTAIN WORKING SPACE AT STORAGE PANEL 110.26
9) USE LISTED CONNECTOR FOR COPPER AND ALUMINUM