Permit: T11EL02091

Parcel: 127071340


Addresses:

5212 E 8TH ST

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/19/2012 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CALLED # NO ANSWER
08/05/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED PROPER COVERS AT ALL EXTERIOR RECEPTS (GFCI) PROTECT
2) MISSING SMOKE DETECTORS IN BEDROOMS/HALLWAY
3) EXPOSED WIRES HALL
4) MISSING FACE PLATES THRU-OUT HOUSE
5) IF YOUR REMODELING NEED PERMITS FROM CITY
6) MAIN SERVICE HAS SEVERAL CODE VIOLATIONS (NEEDS TO BE UPGRADED) WITH CITY PERMITS
7) EXPOSED WIRES AT EXTERIOR/ROMEX NEEDS TO BE IN CONDUIT UNDER 8'
8) THUMB LATCH NEEDED AT EGRESS DOORS (NO KEYED ALLOWED)