Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T11EL00894
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/29/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED SMOKE DETECTORS IN ALL SLEEPING ROOMS AND HALLWAY 2) NEED GFCI PROTECTION ON ALL KITCHEN COUNTER RECEPTS AND ALL EXTERIOR RECEPTS AT GRADE WITH APPROVED BUBBLE COVER 3) NEED GFCI PROTECTION ON ALL KITCHEN COUNTER RECEPTS AND ALL EXTERIOR RECEPTS 4) AT GRADE WITH APPROVED BUBBLE COVERS 5) NEUTRAL BEING USED AS AN UNGROUNDED CONDUCTOR AT MAIN 6) 14 AWG WIRE GOING TO 30 AMP BREAKER ? (2) 7) FEEDER TO LAUNDRY ROOM UNSAFE 8) LAUNDRY ROOM HAS SEVERAL ELECTRIC CODE VIOLATIONS THAT NEED ADDRESSED 9) ALL ELECTRICAL NEEDS TO BE SAFE IN ORDER TO RELEASE POWER |