Permit: T11EL00685

Parcel: 120085100


Addresses:

4863 S 12TH AV

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/14/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BATHROOM RECEPTS TO BE GFCI PROTECTED
2) WATER HEATER NOT CORD AND PLUG APPLIANCE
3) EXPOSED CONDUCTORS BACKROOM
4) GROUNDED RECEPTS ON NON GROUNDED CIRCUITS
5) REMOVE DANGLING RECEPT FROM BELOW PANEL
6) BREAKER TO BE LISTED FOR USE BY MANUFACTURE
7) OLD DISCONNECT NOT FOR USE AS JUNCTION BOX-CONDUCTORS DETERIORATED IN BOX
8) NO PANEL LABELING
9) NO LAST WRITE UP ON SITE