Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T11DV06162

Parcel: 108210060


Addresses:

1369 E PROSPECT LN

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
07/28/2011 INSP - INITIAL CODE ENFORCMENT Approved VISITED SITE, MET WITH TFD CAPT. TONY GONZALEZ WHO MENTIONED THAT UPON ARRIVAL THEY FOUND SMOKE BILLOWING OUT OF THE INTERIOR SUB PANEL AND THAT THE WALL SECTION BELOW THE PANEL WAS HOT TO TOUCH. FOUND TWO LIFELINES RUNNING FROM THE TRAILER TO AN OLDER BOX ON A POST BEING USED AS A PEDESTALL, THEY UNPLUGGED BOTH LIFELINES. TFD INFORMED THE OCCUPANTS THAT THEY WOULD NOT BE ABLE TO STAY AT THE TRAILER AND TFD CONTACTED RED CROSS TO PUT THE TENANTS UP UNTIL REPAIRS COULD BE MADE. OCCUPANTS INFORMED ME THEIR LOT WAS CONSIDERED LOT #B AND THAT SERVICE PANELS THAT PROVIDED POWER TO THEIR LOT WAS INSTALLED NEXT DOOR. WALKED OVER TO THE NEIGHBORING PROPERTY FOUND (3) 100 AMP SERVICE PANELS, ONE FED LOT B, ONE FED LOT #A, AND THE THIRD PANEL FED THE HORSE CORRALS. CALLED TEP TO TURN OFF DISCONNECT INSIDE THE PANEL AND ASKED THEY PUT A LOCK ON THE BOX.
** FOUND BARE WIRE, BURNED WIRING AND BREAKERS INSIDE THE INTERIOR SUB PANEL DUE TO ARCHING. FOUND IMPROPER INSTALLATION OF THE "PEDESTAL" WHICH FED THE A/C UNIT AND THE INTERIOR SUB PANEL. EMERGENCY VACATE NOV WAS ISSUED FOR THE HAZARDOUS ELECTRICAL AND NO A/C AND INCLUDED THE DETERIORATED FLOORING INSIDE THE UNIT.
*RESEARCH FOUND THAT THE (3) SERVICE PANEL LOCATED UNIT # A WERE NEVER PERMITED, CONTACTED OWNER ANN THOMSON INFORMED HERE A PERMIT WOULD BE REQUIRED FOR THE (3) SERVICE PANELS BEFORE SHE COULD MOVE FORWARD WITH THE WORK AT UNIT # B. OWNER INFORMED ME THAT SHE ALREADY APPLIED FOR AN ELECTRICAL REPAIR PERMIT.

OCCUPANT: RAYMOND CASSILLAS 251-3176
OWNER: ANN THOMSON 561-7660